Product Description
Applications:
The K675BIP, 15/25kV basic insulating plug attaches and insulates Elastimold® K675/6BLR, K675BE and K675BVS 900 Amp connectors. It is equipped with a capacitive test point and a molded rubber sealing cap as standard.
Features:
- Fully rated 15/25kV, 900 Amp Deadbreak Insulating Plug
- Can be easily connected or disconnected using standard hand tools and equipment in a de-energized state.
- Hex Nut serves as a Capacitive Test Point
For 15kV Voltage Class:
- 8.3kV Max Phase-to-Ground – Operating Voltage 14.4kV Max Phase-to-Phase
- 95kV BIL – Impulse Withstand (1.2 x 50 microsecond wave)
- 34kV AC – One minute withstand
- 53kV DC – 15 minutes withstand
- 11kV AC – Corona Extinction @ 3pC sensitivity
- 900 Amp – Continuous
- 25kA Sym – 10 Cycles Momentary
For 28kV Voltage Class:
- 16.2kV Max Phase-to-Ground – Operating Voltage 28kV Max Phase-to-Phase
- 140kV BIL – Impulse Withstand (1.2 x 50 microsecond wave)
- 45kV AC – One minute withstand
- 84kV DC – 15 minutes withstand
- 21.5kV AC – Corona Extinction @ 3pC sensitivity
- 900 Amp – Continuous
- 25kA Sym – 10 Cycles Momentary
Payment Terms︰
TT
Standards Certificate︰
IEEE Std 386™-2006
Product Image